An electric shower running on full draws 32A to 50A continuously for the duration of the shower. That's 7,360W to 11,500W. Compare to a kettle: 13A intermittent. A washing machine: 13A peak, falling fast. An oven on full: 16A on a 32A circuit it shares with the hob.
This is why electric showers always need their own dedicated circuit running directly from the consumer unit. Sharing the circuit with anything else would either trip the breaker constantly or overload the cable creating a fire risk. The shower also needs its own RCD or RCBO (residual current device) for shock protection in the wet zone.
Cable size matters. 8.5kW: 6mm twin-and-earth. 9.5kW: 10mm twin-and-earth. 10.8kW: 10mm or sometimes 16mm depending on cable run length. Undersized cable can pass a quick test then overheat under sustained load and cause fire. We size correctly for the shower kW first, then verify cable run length with a voltage-drop calculation.